Prove
All outcomes
Skills

Power Systems Analysis

8 weeks · 0 milestones

Perform a power systems analysis for a defined electrical network — either a real distribution network (using public utility data) or a documented study network. The analysis must cover: a single-line diagram of the network with all bus voltages, line impedances, and load specifications, a load flow analysis calculating real and reactive power flows on all branches and bus voltages under normal operating conditions, a fault analysis calculating fault current for at least one three-phase bolted fault at a specified bus, and a protection coordination analysis identifying whether the existing protection devices (or proposed devices) will correctly isolate the fault. Preferred proof: analysis of a real utility or industrial distribution network using professional software. Accessible alternative: pandapower (Python library, free and open-source) or OpenDSS (free, from EPRI) applied to a published IEEE test network (IEEE 9-bus, 14-bus, or 30-bus systems — all publicly available). Hand calculation for a simplified 3-bus network is also accepted with documented methodology. Proof artifacts: the single-line diagram and network specification (design artifact) and the load flow and fault analysis results (analysis artifact). Verification: a power systems engineer reviews the fault analysis — 'at this fault level, does the upstream breaker clear within its rated interrupting time?' — requiring you to reason through your own protection coordination.

Milestone map

Milestone map

3 milestones

Define the Power System and Model Single-Line Diagram

1–2 weeks (3–4 hrs/week)

Choose a power system to analyse — a distribution network, industrial plant power system, or microgrid. Draw a single-line diagram (SLD) showing all generation sources, transformers, busbars, transmission lines, loads, and protection devices. Assign per-unit (p.u.) base values for the system. A correctly drawn SLD with consistent per-unit bases is the foundation for all subsequent load flow and fault analysis — errors at this stage cascade through every calculation.

Proof required

Submit your system definition: a drawn single-line diagram with all components labelled, per-unit base values stated (MVA base and kV base for each voltage level), and a component list table (generation, transformer, line, load ratings).

What gets checked

  • SLD labels all components with their ratings — transformer MVA/kV, line impedance, generator MVA, load MW/Mvar
  • Per-unit base values are stated for all voltage levels in the system (MVA base + kV base → impedance base for each level)
  • SLD is drawn (not copied from a textbook) with a consistent set of symbols

Common mistakes

  • Using inconsistent base values across voltage levels — per-unit impedances will be wrong if the kV base is not correctly transformed through each transformer
  • Omitting protection devices from the SLD — short-circuit analysis in M2 requires knowing where fuses, breakers, and relays are located

Powstik Guide

A labelled single-line diagram with per-unit bases.

Steps

  1. Define the system boundary.
  2. Draw every bus, line and transformer.
  3. Label ratings on each component.
  4. Choose base MVA and base voltages.

Template

Base MVA:
| Zone | Base kV | Base impedance |
|------|---------|----------------|
Components and ratings:

What gets sent back

  • Unlabelled components.
  • No per-unit bases.
  • Missing transformer zones.

Resources

Foundationstart here

Depthgo deeper

Masteryfor the dedicated

What a verifier looks for

  • Confirm SLD labels all components with their rated values — flag any component shown without a rating.
  • Confirm per-unit base values are stated for every voltage level — confirm kV base changes correctly at each transformer.
  • Confirm SLD is original (not copied from a textbook) — components should match the system selected.

You'll sign in first, then come straight back here.

Perform Load Flow and Short-Circuit Analysis

3–4 weeks (4–5 hrs/week)

Perform a load flow (power flow) analysis to find bus voltages, real and reactive power flows, and transmission losses under normal operating conditions. Use Gauss-Seidel, Newton-Raphson, or a free simulation tool (PSCAD, pandapower, or PyPSA). Then perform a three-phase balanced fault (short-circuit) analysis at ≥2 buses to find fault current magnitudes and confirm protection device ratings are adequate. Both analyses are required — load flow shows normal operation; fault analysis governs protection design.

Proof required

Submit your analysis results: load flow bus voltage table and power flow summary, and fault current calculations at ≥2 buses showing method and per-unit impedance values used.

What gets checked

  • Load flow results show bus voltages within ±5% of nominal — state any buses that violate this and explain why
  • Fault current calculations show per-unit impedance values and base conversion — not just final kA results
  • Analysis covers both normal (load flow) and fault conditions — not one or the other

Common mistakes

  • Running a simulation without understanding what it calculates — verify one result by hand before trusting simulation outputs
  • Fault analysis at only one bus — at minimum analyse the highest-fault-current bus (usually closest to generation) and a remote bus

Resources

Foundationstart here

Depthgo deeper

What a verifier looks for

  • Confirm load flow results include bus voltage magnitudes and angles, plus real/reactive power flow on each line.
  • Confirm at least one result is verified by hand calculation or against a textbook example — not purely simulation output.
  • Confirm fault current calculations show per-unit impedance values and base conversion to physical kA.

You'll sign in first, then come straight back here.

Assess Protection Coordination and Write the Analysis Report

3–4 weeks (2–3 hrs/week)

Using the fault current results from M2, check that protection devices (fuses, circuit breakers, relays) are correctly coordinated: the device closest to the fault operates first, and upstream devices operate only if the downstream device fails. Document the time-current characteristics of each device and the selectivity margins. Write a complete power systems analysis report and have it reviewed by an electrical engineer with power systems experience.

Proof required

Submit your protection coordination assessment (time-current characteristic plot for ≥2 protection devices showing selectivity) and power systems analysis report (≥2,000 words including SLD, load flow results, fault analysis, and protection coordination) plus review record.

What gets checked

  • Time-current characteristic plot shows ≥2 devices with selectivity margins labelled — not just a list of device ratings
  • Report covers all four sections: SLD, load flow, fault analysis, protection coordination
  • Reviewer has electrical engineering (power systems) background — peer review without domain expertise does not count

Common mistakes

  • Describing protection devices without drawing their time-current characteristics — selectivity can only be confirmed visually from the curves, not from ratings alone
  • Writing a report that presents only simulation outputs without interpretation — analysis means explaining what the results mean for the design

Resources

Depthgo deeper

What a verifier looks for

  • Engineering Design Triad check: M1–M3 together produce a design artifact (SLD with per-unit system), an analysis artifact (load flow + fault current calculations + protection coordination plot), and a documentation artifact (complete power systems analysis report + review record) — confirm all three types are present.
  • Confirm time-current characteristic plot shows ≥2 devices with selectivity margins — not just device ratings in a table.
  • Confirm load flow and fault analysis results are interpreted — not just simulation outputs pasted into a report.
  • Confirm reviewer has power systems electrical engineering experience — challenge questions must probe the load flow results and protection coordination logic.
  • The Proof Accessibility Rule applies — pandapower (free), PyPSA (free), PSCAD free educational version, MIT OCW (free), and Schneider free guides are all accessible without commercial licence.

You'll sign in first, then come straight back here.

We use analytics to improve Powstik. No ads, ever.